KYN28柜是一种高压开关柜,具体信息如下:应用范围:KYN28柜适用于三相交流50Hz单母线和双母线分段系统的户内成套配电设备。适用于额定电压3-12kV电网的发电厂、变电站、工矿企业。它用于接收和分配电能,以及控制、保护和监控电路。结构特点:The KYN28 cabinet consists of a fixed cabinet body and a movable vacuum circuit breaker handcart. The cabinet body is divided into four small chambers: busbar chamber, circuit breaker chamber, cable chamber, and low-voltage chamber.
The cabinet structure is made of aluminum zinc coated plate processed by CNC machine using multiple bending processes and bolted together; All operations are carried out with the cabinet door closed; High protection level, which can prevent the invasion of debris and pests; Simple and effective "five prevention" locking to prevent misoperation.
Can be equipped with VS1 and VD4 vacuum circuit breakers; Replacing the circuit breaker is simple, and the handcart has good interchangeability performance; Reliable wall installation and front maintenance of cabinets to reduce floor space; The cable room has ample space and can connect multiple cables; Heaters can be installed separately in the circuit breaker room and cable room to prevent condensation and corrosion.技术参数:Rated voltage: 3.6kV~12kV.
Rated frequency: 50Hz.
Rated current of circuit breaker: 630A, 1250A, 1600A, 2000A, 2500A, 3150A, 4000A.
Rated short-time withstand current (4s): 25kA, 31.5kA, 40kA.
Rated peak withstand current (peak): 63kA, 80kA, 100kA.
Rated short-circuit breaking current: 25kA, 31.5kA, 40kA.
Rated short-circuit closing current (peak): 63kA, 80kA, 100kA.使用环境条件:The altitude shall not exceed 2000m.
The highest temperature is+40 ℃, and the lowest temperature is -5 ℃ (outdoors).
Relative humidity of the environment: daily average not exceeding 95%, monthly average not exceeding 90%.
The seismic intensity shall not exceed 8 degrees.
Vibration, impact, and highly corrosive environments should be avoided.符合标准:KYN28 机柜符合 IEC298 和 GB3906 等技术标准。